<< Click to Display Table of Contents >> Analyzer > Result presentation > Result evaluation > Show Report |
Several different reports are available. The number of reports and their content can change between different customers.
Select a calculation from the tab Results/Administration, Select a calculation, right-click and select Show report.
Select the desired substation in the list, right-click and select the type of report that should be presented.
The last alternative in the right-click menu is Alarm report. The alarm report only displays the alarms in the network.
If there are any alarms, the alarm report is also displayed as a chart. The content of the chart can be different depending on the presentation level.
A-alarms are more serious than B-alarms.
Voltage drop %
LV < 1.0 kV 5 > % will result in an A-alarm
MV > 1.0 kV 5 > % will result in an A-alarm
Relative conductor load (load current compared to rated conductor current)
90 – 100 % will give a B-alarm
100 > % will give an A-alarm
Fuse alarm. Tripping time is above allowed value in the parameter set.
A too long time will give an A-alarm
Voltage < 207 V will give an A-alarm
Voltage > 244 V will give an A-alarm
Relative fuse load (load current against the rated current of the fuse)
80 – 100 % will give a B-alarm
100 > % will give an A-alarm
Transformer load 1-25kV
90 – 100 % will give a B-alarm
100 > % will give an A-alarm
By using the tool buttons in the chart, it is possible to Select series, Display value
, Zoom in/out
and Pan
.
With the file menu it is possible to Export to PDF and Close application window.
With the settings menu it is possible to select the checkboxes Grid, Legend and Log y and it is also possible to Adjust Colors, Set labels and Add titles.
The checkbox Grid adds a grid to the chart.
The checkbox Legend adds a legend to the chart.
The checkbox Log y logs y to the chart.
Adjust Colors opens the color palette dialog which allows you to change the color for the chart.
Set labels opens the dialog Set labels which allows you to change the labels for x and y axis.
Add titles opens the dialog Add titles which allows you to change the header, sub-header or footer.