<< Click to Display Table of Contents >> Analyzer > Appendix > Result terminology > Conductor result terms |
Term Long text |
Short text |
UNIT |
Description |
---|---|---|---|
Active conductor power |
A power |
kW |
Active power flow in cable |
Active power losses |
A P.loss |
kW |
Active power losses in cable |
Additional length |
Add length |
m |
Additional length |
Alarm 1-sec current |
Alarm shortcircuit current |
|
Alarm from the calculation core, related to the short-time withstand current of the line type. Is either empty, “A” or “T” (T=alarm based on the short-circuit current of the to-point |
Alarm Cab% |
Alarm Cab% |
|
Alarm obtained from the parameter settings for the relative load-level of the cables (Relative load current) |
Alarm fuse tripping time |
Alarm Ie |
|
Alarm from the calculation core relating max allowed trip time for protection. Differs for MV, LV and LV service cables |
Alarm Fuse% |
Alarm Fuse% |
|
Alarm obtained from the parameter settings for the relative load of the cables (Relative fuse-load) |
Alarm Ijs |
Alarm Ijs |
|
Alarm obtained from parameter settings for alarm for the tripping time of the fuses (Alarm Fuse Ij) |
Alarm neutral conductor strength |
Alarm neutral shortcircuit |
|
Alarm from the calculation core, related to the short-time withstand current of the neutral conductor |
Calculation length |
Calc.l |
m |
Length in meter as basis for the calculation |
C-factor |
C-fact |
|
Used C-factor for correcting earth fault current (LV), derived from protected protection, from calculation parameters, and cable rating |
Conductor current |
Current |
A |
Load current through the cable |
Line type |
Line type |
|
Line type |
Energy losses |
En.loss |
kWh |
Conductor energy losses |
Feed order |
Feed order |
|
The feeding order from the calculation core, sequence number |
Fuse F Current |
Ifuse 1 |
A |
Fuse rated current in the conductors from end |
Fuse F Make |
Ifuse 1 Make |
|
Fuse make in the conductors from end |
Fuse T Current |
Ifuse 2 |
A |
Fuse rated current in the conductors to end |
Fuse T Make |
Ifuse 2 Make |
|
Fuse make in the conductors from to |
Graphical length |
G-Length |
m |
Conductor graphical length |
Load loss cost |
Loss cost |
Currency |
Capitalized cost of load losses based on price, year and interest in the calculation parameters |
Lp Date max current |
Date max curr. |
|
Date when max current appears for a section when using load pattern curves as load input |
Lp Hour max current |
HH max curr. |
|
Hour for given date when max current appears for a section when using load pattern curves as load input |
Lp Max current |
Max curr. |
A |
Max current for given date and hour for a section when using load pattern curves as load input |
Lp Max relative current |
Max rel.curr. |
% |
Max current in relation to rated current for given date and hour for a section when using load pattern curves as load input |
Max fuse |
Max fuse |
A |
Maximum allowed fuse. Is based on the specified type of fuse in the calculation parameters, and the lowest fuse of other max calculated fuses |
Max fuse Ij |
Max fuse Ij |
A |
Maximum allowed fuse relating to earth fault current. Based on specified trip times calculation parameters. LV. |
Max fuse Ik2 |
Max fuse Ik2 |
A |
Maximum allowed fuse relating to 2 phase short circuit current. Based on specified trip times and type of fuses in the calculation parameters. MV |
Max fuse Ik3 |
Max fuse Ik3 |
A |
Maximum allowed fuse relating to 3 phase short-circuit current. Based on specified trip times and type of fuses in the calculation parameters. LV + MV. |
Max fuse rated current |
Max fuse curr. |
A |
Maximum allowed fuse related to the rated current for the cable in the calculation parameters. Code-list: NETCALC.CALC_MAXFUSE_CL |
Measured length |
M-length |
m |
The documented length of the cable |
Min fuse |
Min fuse |
A |
Minimum allowed fuse that can be used depending on the load current of the conductor and type of fuses in the calculation parameters. LV + MV. |
Node from |
Node from |
|
The ID for the from point of the conductor, if it can be deduced |
Node to |
Node to |
|
The ID for the to point of the conductor, if it can be deduced |
Node, Lowest current in loop |
Node Imin |
|
The ID of the node point where the lowest current in a loop will occur. This will bee seen in meshed/looped networks only. |
Pointer to active protection |
Protect sequence |
|
Serial number as reference to a protected protection. Every protection gets a unique serial number |
Proposed make |
Proposed make |
|
The proposed make together with fuse size uniquely identifies the systems proposed protection |
Prot.device tripping current |
Itrip prot. |
A |
Protecting protection specified current or similar. E.g. or start-current in a relay |
Protected make |
Protected make |
|
Make / type for the protection that has been identified as protected protection for the section |
Protected rated current |
Protected rated current |
A |
Rated current for the designated protected protection in the section |
Protective device rated current |
Irate prot. |
A |
Rated current for the designated protected protection in the section |
Reactive conductor power |
R power |
kVAr |
Reactive power flow through the cable |
Reactive power losses |
R loss |
kVAr |
Reactive power losses through the cable |
Relative fuse load |
Rel.fuseload |
|
Relative load current based on calculated load current and rated current of the fuse |
Relative load current |
Rel.curr |
% |
Relative load current based on calculated load current and max allowed specified current in code list with rated types |
Sel alarm |
Sel alarm |
|
Selectivity alarm. A fuse in the section is non-selective towards another overlying fuse |
Sum capacitive earth fault currents |
Sum cap curr |
A |
Total capacitive current generated by the network. |
Sum other capacitive currents |
Sum oth cap curr |
A |
Sum of additional added capacitive currents |
Sum reactor currents |
Sum react.curr |
A |
The sum of reactive currents through the reactors. |
Sum resistor currents |
Sum res.curr |
A |
The sum of active currents through the resistors. |
Trip time Ij |
Triptime Ij |
sec |
Tripping time based on the lowest earth fault current (LV) |
Trip time Ik2 |
Triptime Ik2 |
sec |
Tripping time based on the lowest two phased short-circuit current (MV) |
Trip time Ik3 |
Triptime Ik3 |
sec |
Tripping time for relay/fuse related to the highest calculated short circuit current (Ik3) |
Trip time relay max fault current |
Triptime relay maxfaultcurrent |
sec |
Tripping time for securing relay relating to lowest calculated short-circuit current (Ij or Ik2) |
Trip time relay min fault current |
Triptime relay minfaultcurrent |
sec |
Tripping time for securing relay relating to the highest calculated short-circuit current (Ik3) |
Tripping time Ie |
Tr.time Ie |
sec |
Tripping time for an earth fault. |
Tripping time Ik2 |
Tr.time Ik2 |
sec |
Tripping time för a phase to phase fault. |
Visualization col.numb |
Color |
|
The nimber of a color used when visually displaying different result values. |
Zone number |
Zon no |
|
The number of the current zone when calculating on capacitive zonez |