<< Click to Display Table of Contents >>
Term Long text |
Short text |
UNIT |
Description |
3-Phase active shc power |
Pk3 |
kW |
Active three phase short circuit power calculated in node-point |
3-phase apparent shc power |
Sk3 |
kVA |
Apparent three phase short circuit power calculated in node-point |
3-Phase reactive shc power |
Qk3 |
kVAr |
Reactive three phase short circuit power calculated in node-point |
Active power |
A pow |
kW |
Node point active power |
Alarm U% |
Alarm U% |
|
Alarm obtained from parameter settings relating to the relative voltage drop for node points |
Alarm V |
Alarm V |
|
Alarm obtained from parameter settings relating to voltage for node points |
Base Voltage |
Base Volt. |
kV |
System voltage for the node-point (based on sub-type in the documentation) |
Customer fuse |
Cust.fuse |
A |
Customer fuse rated current. Only information about customer fuses are available via the customer system |
Double earth fault |
Double e.fault |
A |
Only calculated in point with earth point according to simplified method, 2 faults in the same point (twin-case) in MV. |
Earth fault current |
Ie |
A |
Earth fault current at direct earthed network for simulated error in the node-point. LV |
Earth fault impedance |
Earth imp. |
ohm |
Earth fault impedance in the point. The impedance that is the basis for the earth fault currents in the point. Direct earthed LV-net |
Earth fault voltage LV |
E.fault.volt.LV |
V |
The exposed voltage in in the node point at earth fault in direct earthed LV network |
Earth fault voltage MV |
E.fault.volt.MV |
V |
The exposed voltage in in the node point at earth fault in impedance earthed Mv network |
Energy read |
En inp. |
kWh |
Total energy for the nodepoint from attached customers |
Ik2 |
Ik2 |
A |
Phase to phase shortcircuit current for simulated error in node point. MV |
Ik3 |
Ik3 |
A |
Three phase short circuit current for simulated error in node point. MV + LV |
Ik3 transformer upside |
Ik3 trf.prim |
A |
Three-phased short-circuit current for simulated error in downside of the transformer, re-calculated to upper-side. MV + LV |
Load current in load point |
I n.point |
A |
Load current generated by the load attached to the specific node point |
Lp Date min voltage |
Date min V. |
|
Date when minimum voltage for the node appears when making a calculation using load profile curves for load input |
Lp Hour min voltage |
HH min V. |
|
Hour for the date when minimum voltage for the node appears when making a calculation using load profile curves for load input |
Lp Min voltage |
Min V. |
kV |
The minimum voltage for the node at date and hour for minimum voltage when making a calculation using load profile curves for load input |
Max exposed earthfault voltage |
Max exp.volt. |
V |
Maximum allowed exposed voltage at earth faults |
Node |
Node |
|
ID for the node point |
Positive seq.imp. |
Pos.imp. |
ohm |
The node point positive sequence impedance |
Powermagin max current |
Pmarg.I/P |
kW |
Power margin relating to feeding components load limits, conductors and transformers. |
Powermagin voltage drop |
Pmarg Vdrop |
kW |
Power margin relating to the max allowed voltage-drop in the node points of the network. Specified in the calculation parameters |
PQ margin Type |
PQm |
|
A flag for power type, which is limiting in the margin calculation. P = active , Q = reactive. |
Reactive power |
R pow |
kVAr |
Reactive power as load on the node point. Can be Velander calculated power and/or read power depending on input data |
Rk earth |
Rk earth |
Ohm |
Earth fault resistance in node-point |
Rk phase |
Rk phase |
Ohm |
Short circuit resistance phase conductor, positive sequence, calculated in node-point |
Rk zero |
Rk0 |
Ohm |
Short circuit resistance neutral conductor, zero sequence, calculated in node-point |
Single phase shortcircuit |
Ik1 |
A |
Single phase short circuit or short circuit phase-screen MV. |
Sum cable earth capacitances from above |
Sum earth cap u |
A |
The sum of earth capacitances for conductors (re-calculated to capacitive current), contribution from overlying network relating to this node point |
Sum cable earth capacitances from below |
Sum earth cap d |
A |
The sum of earth capacitances for conductors (re-calculated to capacitive current), contribution from underlying network relating to this node point |
Sum Cable operating capacitance from below |
Sum operating cap d |
kVAr |
The sum of operating capacitances for conductors (re-calculated to reactive power), contribution from underlying network relating to this node point |
Sum neutral point reactor current from above |
Sum curr reactor u |
A |
The sum of neutral point reactor current from overlying network relating to this node point |
Sum neutral point reactor current from below |
Sum curr groundreactor d |
A |
The sum of neutral point reactor current from underlying network relating to this node point |
Sum oth. capacitive current from neutral point from above |
Sum oth cap cur u |
A |
The sum of other capacitive current in neutral points from overlying network relating to this node point |
Sum oth. capacitive current from neutral point from below |
Sum oth cap cur d |
A |
The sum of other capacitive current in neutral points from underlying network relating to this node point |
Sum reactive current from above |
Sum reactive cur u |
A |
Sum of reactive current (capacitances less the inductive current). Contribution from overlying network in relation to the point |
Sum reactive current from below |
Sum reactive cur d |
A |
Sum of reactive current (capacitances less the inductive current). Contribution from underlying network in relation to the point |
Sum resistive current from above |
Sum resistive cur u |
A |
Sum of resistive current from active reactor losses. Contribution from overlying reactors relative the point |
Sum resistive current from below |
Sum resistive cur d |
A |
Sum of resistive current from active reactor losses. Contribution from underlying reactors relative the point |
Voltage |
Volt. |
V |
Calculated voltage in node-point |
Voltage angle |
Ang grd |
Grd |
Calculated voltage angle in node-point relating to angle in the feeding point |
Voltage drop |
V.drop |
% |
Voltage drop calculated in relation to overlying transformer downside (lower busbar) |
Voltage rigidity |
U rig. |
% |
Voltage drop calculated for simulated impulse load (voltage rigidity), based on stated impulse load power in the calculation parameters |
Xk earth |
Xk earth |
Ohm |
Earth fault reactance calculated in node-point |
Xk phase |
Xk phase |
Ohm |
Phase conductor reactance calculated in node-point |
Xk zero |
Xk0 |
Ohm |
Neutral conductor reactance calculated in node-point |