Unbalanced calculations

<< Click to Display Table of Contents >>

Unbalanced calculations

 

Introduction to unbalanced calculations in dpPower Analyzer

Both load flow and fault current calculations can be performed for unbalanced networks.

 

Conditions

The calculation can be performed both for LV and MV networks and the trace can be started from any optional point in the network.

If there is no description of the phase code for the conductor it is assumed to be a normal 3-phase distribution conductor. If the load points do not have a specific phase code they are assumed to have a symmetric 3 phase load.

As start voltage for the calculation the phase voltage is used. Only the value for phase 1 is needed, since the calculation automatically will set the start values for the other phases to the same value. If all start voltages are set they will all be used in the calculation.

Phase codes are entered in the attribute form, tab Project load. Press Add and enter the desired Phase code in the drop-down list.

 

Limitations

No meshes are allowed

No parallel transformers are allowed

No one-phase transformers are allowed

 

Error printouts are obtained for:

If the conductor has a phase code that is not included in the nearest feeding conductor

If the load-point has a phase code that is not included in the phase code of the feeding conductor

Parallel transformers

Parallel conductors can only be calculated for a 3 phase configuration

 

Result terms

1.Volt 1

2.Volt 2

3.Volt 3

4.Angle 1

5.Angle 2

6.Angle 3

7.Voltage drop 1

8.Voltage drop 2

9.Voltage drop 3

10.conductor current 1

11.conductor current 2

12.conductor current 3

13.Total current

14.Relative load-current 1

15.Relative load-current 2

16.Relative load-current 3

17.Active losses 1

18.Active losses 2

19.Active losses 3

20.Reactive losses 1

21.Reactive losses 2

22.Reactive losses 3

23.Three-phase active short-circuit power

24.Three-phase reactive short-circuit power

25.Three-phase apparent short-circuit power

26.Three-phase current in Node-point

27.Two-phase current in Node-point

28.Short-circuit phase-zero Ij in a node (if no generators this gives the result)

29.Short-circuit phase-zero 1 in a node L1-phase

30.Short-circuit phase-zero 2 in a node L2-phase

31.Short-circuit phase-zero 3 in a node L3-phase

32.Zk Positive

33.Rk Positive

34.Xk Positive

35.Three-phase current in conductor

36.Two-phase current in conductor

37.Short-circuit current phase neutral/ground in conductor (if no generators this gives the result)

38.Short-circuit current phase neutral/ground 1 in conductor from above.

39.Short-circuit current phase neutral/ground 2 in conductor from above.

40.Short-circuit current phase neutral/ground 3 in conductor from above.

41.Short-circuit current phase neutral/ground 1 in conductor from bottom.

42.Short-circuit current phase neutral/ground 2 in conductor from bottom.

43.Short-circuit current phase neutral/ground 3 in conductor from bottom.

44.Protection make

45.Protection rated current

46.Suggested make

47.Suggested maximum fuse IkMax (Based on maximum current of three, two and one-phase current)

48.Suggested maximum fuse IkMin (Based on maximum current of three, two and one-phase current)

49.Suggested minimum fuse

50.Suggested maximum fuse

51.Tripping time IkMax

52.Tripping time IkMin

53.Alarm conductor short time current

 

 

Calculation example

Make sure a delivery point has an unbalanced load by setting the phase code of a delivery point to L1-N. The load will be located between Phase L1 and neutral.

Make sure the conductor will include the correct phases (Phase L1-Neutral).

 

Result template

Make sure you have a result template with desired non symmetrical calculation results available. In the example - voltages and currents.

 

Start the calculation trace the same way as for a symmetric network calculation.

Select the unbalanced calculation and set at least one phase feeding point voltage as a start value.

Use the correct result template and show the result in the map.

 

Study the current direction phase by phase. Only one phase carries current.

 

Use fixed reports for further analysis.

 

Single phase generators
The generator is documented as a standard distribution generator but the correct phase code must be specified.

 

Map result presentation

The result for an individual conductor can be presented in a tabular form.

 

Conductors

For the conductors both fault currents from the feeding point and downwards to the faulty point and fault currents from the faulty point and upwards will be presented
 
Fault currents from above will receive contributions from other generators in the network and the feeding point. (Excluding any generation in fault object itself). The smallest of these fault currents will be the input for the protection tripping time evaluation.

Fault currents from below, will receive contributions from generators below the conductor in the feeding order.

Nodes

For the nodes the fault current is shown phase by phase. Contributions from all involved generators in the network, including any generator in the object itself as well as from the supply point will be presented.

 

Three-phase unbalanced load flow

This section includes theory and solution of three-phase unbalanced load flow.

 

Line section representation

In a distribution system where balanced transposition of conductors is assumed (impedance symmetrical systems) and balanced three-phase loads at the customers dominate a single phase representation is commonly used in load flow studies. The phase inductance then includes the self impedance and the mutual inductance with the other two phases. If these prerequisites are not fulfilled a full three-phase representation must be used

 

 

 VRR´ , VSS´ , VTT´  and VNN´ are voltage drops on the three phases        

 and the neutral

 

 ZR , ZS , ZT and ZN are the self impedances

 

 ZRS , ZST and ZRT  are the phase to phase mutual impedances

 

 ZRN , ZSN and ZRN  are the phase to neutral mutual impedances

 

 IR , IS , IT and IN are the currents in the phases and the neutral        

 

In a multi-grounded system we can assume that

 

 VNN´ = 0                                                                        (2)

 

 

 

 

 

If we can assume that the system is impedance symmetrical the impedance data is simplified to

 

 ZR= ZS = ZT = ZE                                                        (7)

 

 ZRS = ZST = ZRT = ZÖ                                                (8)

 

 ZRN = ZSN = ZRN = ZNÖ                                                (9)        

 

 

 

 

 

For a section with only one phase and grounded neutral almost all of the phase current returns in the neutral conductor,

 

 

Line section with a single phase and grounded neutral

The voltage drop across the phase conductor is calculated as

 

         VRR´ = VRN - VR´N

 

         = ZR IR + ZRN IN - ( ZN IN + ZRN IR )                        (13)

 

Inserting IN = - IR in eq. (13) gives

 

 VRR´ = ( ZR - 2 ZRN + ZN ) IR                                        (14)

 

In conclusion, for the three phase load flow we use a impedance matrix for three phase sections. For two phase sections the matrix contains zeros for the missing phase. For single phase sections we use a single matrix element according to eq. (14).

 

 

Load representation

 

For phase to neutral connected loads the load currents are calculated as

 IR = (SR / VRN) *

 IS  = (SS / VSN) *                                                                (15)

 

 IR = (ST / VTN) *        

 

where

 

 SR , SS and ST are the complex power loads on the three phases

 IR , IS and IT are the complex currents

 VRN , VSN and VTN are the complex phase to neutral voltages

For phase to phase connected loads we use a load representation

 

The complex phase currents and phase to phase voltages are calculated as

 

 IR = IRS - ITR

 IS = IST - IRS                                                                (16)

 IT = ITR - IST

 

 VRS = VR - VS

 VST = VS - VT                                                                (17)

 VTR = VT - VR

 

where

 

 IR , IS and IT are the complex phase currents

 IRS , IST and ITR are the complex phase to phase currents

 VR , VS and VT are the complex phase to ground voltages

 VRS , VST and VTR are the complex phase to phase voltages

 

Given the phase to phase complex power loads SRS , SST  and STR the phase to phase currents are obtained as

 

 IRS = ( SRS / VRS ) *

 IST = ( SST / VST ) *                                                        (18)

 ITR = ( STR / VTR ) *

 

from which the phase currents are obtained according to eq. (16).

 

Load flow solution method

 

For solution of the load flow we use a two step iterative method. In step one, the backward sweep, we calculate and sum up the phase load currents towards the feeding point (slack bus). In step two, the forward sweep, we calculate and sum up the voltage drops towards the end points of the network. We assume that the network is radially configured in normal operation(*), and use an efficient tree labeling technique in the forward and backward sweep procedures.

The solution starts with all voltages set equal to the given feeding point voltage. For each iteration the two step sweep procedures are performed, and the iterations proceed until the calculated voltage correction at the worst bus is below given threshold values for the real and imaginary parts of the voltage.

(*)        In our program for balanced load flows we use a compensation technique to handle meshes in the network. This is not yet included in this program.

 

Fault calculations

 

Beside the load flow we also calculate fault currents for three phase, two phase and single phase (phase to neutral) faults. The fault currents are calculated as

 I3ph = Vph /(ZE - ZÖ)                                                        (19)

 I2ph = Vph-ph /(2(ZE - ZÖ))                                                (20)

 Iph-n = Vph /(ZE - 2 Z+ZN)                                        (21)

where

 I3ph, I2ph and Iph-n are the three phase, the two phase and the phase to neutral fault currents, respectively

 Vph and Vph-ph are the phase to ground and phase to phase voltages

 ZE , ZÖ , ZN and Z are the resulting (from the faulted bus to the        feeding point, including the feeding point fault impedance) self and mutual impedance of the phases and self and mutual impedance of the                                        neutral, respectively.

 

Coincidence of load

 

Coincidence of load is considered by representing the bus load Sk = Pk + jQk as a random variable with mean , (Pk)mean , (Qk)mean , and standard deviation ,  δPk , δQk. The load is assumed to be normally distributed, so that

 

 (Pk- (Pk)mean)/δPk = N(0,1)

 (Qk- (Qk)mean)/δQk = N(0,1)

 

Although Pk and Qk are not known, a statement can be made as to maximum values (Pk)max , (Qk)max , given with some probability p not being exceeded.

 

 (Pk)max = (Pk)mean+ ΔPk

 (Qk)max = (Qk)mean+ ΔQk

 

ΔPk is obtained from the condition

 

 Prob((Pk- (Pk)mean)/δPk < kp ) = p

 

 ΔPk = kp δPk

 

where kp is obtained from a normal distribution table. ΔQk is obtained in the same manner.

 

In order to facilitate a convenient data input to the computer program we have assumed that ΔPk = kp δPk is specified by a factor Δk

 

ΔPk =  Δk (Pk)max

where (Pk)max is the bus load value given as input. ΔQk is obtained in the corresponding way.

From these input values the mean and variance of the bus phase load currents are calculated. The mean and variance of the branch currents, an thus their maximum values, are then obtained in the backward sweep of the load flow by summing up separately the mean and the variance of the phase load currents. In the forward sweep the voltage drop in each branch is calculated from its maximum branch current.