<< Click to Display Table of Contents >> Analyzer > Historical measurements & Load profiles > Results |
If the prognosis and the normal calculation went through, a summarized report can be retrieved.
LOG AFTER LOAD PROFILE CALCULATION
--------------------------------------------------------------------------------------------------------------
Description :
Start date :2017-12-20 Start hour :01
End date :2017-12-20 End hour :24
Used temperature set :Typiskt år Arlanda
Manual stated wind speed :0.0
Edge probability :95.0
Complete loadflow and fault analysis calculation is performed for hour with max power
--------------------------------------------------------------------------------------------------------------
Time of maximum load date :2017-12-20 Hour :19 Active power :126.11 kW
Time of minimum load date :2017-12-20 Hour :16 Active power :78.06 kW
Time of maximum load date :2017-12-20 Hour :19 Reactive power :49.84 kVAr
Time of minimum load date :2017-12-20 Hour :16 Reactive power :30.85 kVAr
Time of maximum load including deviation date :2017-12-20 Hour :19 Active power :134.17 kW
Time of minimum load including deviation date :2017-12-20 Hour :16 Active power :83.74 kW
Time of maximum load including deviation date :2017-12-20 Hour :19 Reactive power :54.91 kVAr
Time of minimum load including deviation date :2017-12-20 Hour :16 Reactive power :34.42 kVAr
--------------------------------------------------------------------------------------------------------------
Number of meters with load profiles curves :4
Total read kWh from load profiles :2308.66 kWh
--------------------------------------------------------------------------------------------------------------
SUMMARY IN FEEDER POINT - LOSSES
Maximal power losses summarized to feeding point :0.5
Mean power losses summarized to feeding point :0.4
Time of maximum power losses :2017-12-20 / 09
Maximum energy losses summarized to feeding point :6.7
Mean energy losses summarized to feeding point :5.3
Maximum energy loss cost summarized in feeding point :0.0
Mean energy loss cost summarized to feeding point :0.0
Maximum capitalized energy loss cost summarized to feeding point :0.0
Mean capitalized energy loss cost summarized to feeding point :0.0
Maximum wighted power loss cost summarized to feeding point :0.0
Mean wighted power loss cost summarized to feeding point :0.0
Maximal wighted capitalized power loss cost summarized to feeding point :0.0
Maximal wighted capitalized power loss cost summarized to feeding point :0.0
SUMMARIZED TRANSFORMERS NO LOAD LOSSES
Summarized no load power losses :0.0
Summarized no load energy losses :0.0
Summarized wighted no load power losses :0.0
Summarized no load energy loss cost :0.0
Summarized wighted capitalized no load power losses :0.0
Summarized capitalized no load energy loss cost :0.0
There are 5 stored summaries from the prognosis calculation. The summaries are not edited and will only display the name of the database fields as headers in the reports.
Table name: netcalc.res_node_load
Field name |
Description |
Calculation ID |
ID of the calculation. |
System ID |
Object ID. |
Object type |
Otype. |
Node id |
ID for the node. |
Node u min |
Lowest voltage kV, Extreme value. |
Node u min proc |
Highest voltage drop %, Extreme value. |
Node u min date |
Year, Month, Day, Lowest voltage. |
Node u min time |
Hour for lowest voltage. |
Node u mean |
Lowest voltage kV Mean value. |
Node u proc mean |
Highest voltage drop %, Mean value. |
Table name: netcalc.res_line_load
Field name |
Description |
Calculation ID |
ID of the calculation. |
System ID |
Object ID. |
Object type |
Otype. |
Node from id |
ID for the node From. |
Node to id |
ID for the node To. |
Line load max |
The maximum conductor current A, Extreme value. |
Line load proc max |
Maximum percentage conductor current %, Extreme value. |
Line max date |
Year, Month, Day, maximum conductor current. |
Line max time |
Hour for maximum conductor current. |
Line max skva |
Maximum apparent power kVA, Extreme value. |
Line max p |
Maximum active power kW, Extreme value. |
Line max p date |
Year, Month, Day, maximum active power. |
Line max p time |
Hour for maximum active power. |
Line max q |
Maximum reactive power kVAr, Extreme value. |
Line max q date |
Year, Month, Day, maximum reactive power. |
Line max q time |
Hour for maximum reactive power. |
Line load mean |
Maximum conductor current A, Mean value. |
Line load proc mean |
Maximum percentage conductor current %, Mean value. |
Line mean p |
Maximum active power kW, Mean value. |
Line mean q |
Maximum reactive power kVAr, Mean value. |
Table name: netcalc.res_trf_load
Field name |
Description |
Calculation ID |
ID of the calculation. |
System ID |
Object ID. |
Object type |
Otype. |
Stn id |
ID for the station. |
Trf id |
ID for the transformer. |
Trf load max |
The maximum transformer load kVA, Extreme value. |
Trf load proc max |
Maximum relative transformer load %, Extreme value. |
Trf max date |
Year, Month, Day, maximum transformer load. |
Trf max time |
Hour for maximum transformer load. |
Trf max p |
Maximum active power kW, Extreme value. |
Trf max p date |
Year, Month, Day, maximum active power. |
Trf max p time |
Hour for maximum active power. |
Trf max q |
Maximum reactive power kVAr, Extreme value. |
Trf max q date |
Year, Month, Day, maximum reactive power. |
Trf max q time |
Hour for maximum reactive power. |
Trf load mean |
Maximum transformer load kVA, Mean value. |
Trf load proc mean |
Maximum percentage transformer load %, Mean value. |
Trf mean p |
Maximum active power kW, Mean value. |
Trf mean q |
Maximum reactive power kVAr, Mean value. |
Table name: netcalc.res_trf_load
Field name |
Description |
Calculation ID |
ID of the calculation. |
System ID |
Object ID. |
Object type |
Otype. |
Node from id |
ID for the node From. |
Node to id |
ID for the node To. |
Line loss p |
Maximum active loss kW for the conductor, Extreme value. |
Line loss q |
Maximum reactive loss kVAr for the conductor, Extreme value. |
Line loss p sum |
Summarized underlying maximum active losses, Extreme value. |
Line loss q sum |
Summarized underlying maximum reactive losses, Extreme value. |
Line loss date |
Year, Month, Day maximum losses power. |
Line loss time |
Hour for maximum losses power. |
Line loss p mean |
Maximum active loss kW for the conductor, Mean value. |
Line loss q mean |
Maximum reactive loss kVA for the conductor, Mean value. |
Line loss p sum m |
Summarized underlying maximum active losses, Mean value. |
Line loss q sum m |
Summarized underlying maximum reactive losses, Mean value. |
Line loss w |
Maximum energy losses kWh for the conductor, Extreme value. |
Line loss w sum |
Summarized underlying maximum energy losses, Extreme value. |
Line loss w mean |
Maximum energy losses kWh for the conductor, Mean value. |
Line loss w sum mean |
Summarized underlying maximum energy losses, Mean value. |
Line loss w cost |
Maximum energy loss cost for the conductor, Extreme value. |
Line loss w cost sum |
Summarized underlying maximum energy loss costs, Extreme value. |
Line loss w cost m |
Maximum energy loss cost for the conductor, Mean value. |
Line loss w cost sum m |
Summarized underlying maximum energy loss costs, Mean value. |
Line loss p cost |
Maximum active power loss costs for the conductor, Extreme value. |
Line loss p cost sum |
Summarized underlying maximum active power loss costs, Extreme value. |
Line loss p cost m |
Maximum active power loss costs for the conductor, Mean value. |
Line loss p cost sum m |
Summarized underlying maximum active power loss costs, Mean value. |
Line trf no load sum m |
The no load power losses for the transformers underlying the conductor, Mean value. |
Table name: netcalc.res_trf_load
Field name |
Description |
Calculation ID |
ID of the calculation. |
System ID |
Object ID. |
Object type |
Otype. |
Stn id |
ID for the station. |
Trf id |
ID for the transformer. |
Trf loss p |
The maximum active loss kW for the transformer, Extreme value. |
Trf loss q |
The maximum reactive loss kVAr for the transformer, Extreme value. |
Trf loss p sum |
Summarized underlying maximum active losses, Extreme value. |
Trf loss q sum |
Summarized underlying maximum reactive losses, Extreme value. |
Trf loss date |
Year, Month, Day maximum power loss. |
Trf loss time |
Hour maximum power loss. |
Trf loss p mean |
Maximum active loss kW for the transformer, Mean value. |
Trf loss q mean |
Maximum reactive loss kVA for the transformer, Mean value. |
Trf loss p sum m |
Summarized underlying maximum active losses, Mean value. |
Trf loss q sum m |
Summarized underlying maximum reactive losses, Mean value. |
Trf loss w |
Maximum energy losses kWh for the transformer, Extreme value. |
Trf loss w sum |
Summarized underlying maximum energy losses, Extreme value. |
Trf loss w mean |
Maximum energy losses kWh for the transformer, Mean value. |
Trf loss w sum mean |
Summarized underlying maximum energy losses, Mean value. |
Trf loss w cost |
Maximum energi loss costs for the transformer, Extreme value. |
Trf loss w cost sum |
Summarized underlying maximum energy loss costs, Extreme value. |
Trf loss w cost m |
Maximum energi loss costs for the transformer, Mean value. |
Trf loss w cost sum m |
Summarized underlying maximum energy loss costs, Mean value. |
Trf loss p cost |
Maximum active power loss costs for the transformer, Extreme value. |
Trf loss p cost sum |
Summarized underlying maximum active power loss costs, Extreme value. |
Trf loss p cost m |
Maximum active power loss costs for the transformer, Mean value. |
Trf loss p cost sum m |
Summarized underlying maximum active power loss costs, Mean value. |
Trf no load sum m |
The no load power losses for the transformers underlying the transformer, Mean value. |
If individual results are requested, it is possible to retrieve them as line charts after a calculation. The result is only saved until the next load calculation is performed since the volume in the result table tends to get very large very fast.
The graphic is displayed by using the right-click menu on a calculated object.
Calculated values > Hour values > Result graphic
For the cable it is possible to request result, load current and/or relative load current.
Example of a conductor current displayed in a chart.
If results are saved for each hour, it is also possible to use a variant of the usual result presentation in a map / schedule to color the grid depending on the calculation result. You must then use a presentation template that contains one of the result terms in (H) in the start form.
Right-click on a calculation result and select Show hourly value result in map.
The network is now colored according to the presentation template, and a window with an explanation opens.
Via the slider under the legend, it is possible to set the hour for which the result is to be presented.
You can also view results in charts for selected objects from here by using the chart icon.
There is a special report for load profile calculations if you have selected to perform a complete calculation at the same time as the prognosis.
The report presents all the maximum current/maximum relative current for the conductors and the lowest voltage and time for the nodes during the requested calculation interval.
Right-click on an object that has stored load profiles.
Select Calculated values > Hour values > Result graphic
All the curves from one day that are stored will be displayed. Only the active curve including the spread.
Display the curve that was used as input for the last prognosis/calculation
The prerequisite is that the input curves are saved in the database. Only the input data for the latest calculation is saved.
The input data curves are retrieved interactively through the interface.
If you right-click on an object that has a stored load profile and was a part of the latest calculation, the alternative Input to calculation graphics is available:
Calculated values > Hour values > Input to calculation graphic
Thanks to the function of displaying extreme values in the map / table, the results of value calculations, for each object it is possible to display: the highest load, the lowest voltage, etc. in the calculated period of time.
Functions are added in the drop-down menu (right-click) on a load profile calculation.
Show result in map > Extreme values
Show result table > Extreme values