<< Click to Display Table of Contents >> Analyzer > Appendix > Result terminology > Total result terms |
Term long text |
Short text |
UNIT |
Description |
Tot active energy load |
W act.tot.inp. |
kW |
Total active load from energy loads recalculated with Velander formula. Summary from all underlying parts. Presented for substations and bays |
Tot active load losses |
P tot.loss. |
kW |
Total active power losses from both load flow losses and no load losses in conductors and transformers. Summary from all underlying parts. Presented for sub-stations and bays |
Tot active no load losses |
P tot noload loss |
kW |
Total active no load power from all underlying trans-formers. Summary from all underlying network parts. Presented for substations and bays |
Tot active power |
P tot |
kW |
Total active power (power flow). Presented for sub-stations and bays |
Tot active power input |
P tot.inp. |
kW |
Total read active power load. Summary from all underlying network parts. Presented for sub-stations and bays |
Tot apparent power |
S tot |
kVA |
Total apparent power. Presented for sub-stations and bays |
Tot energy input |
W tot.inp. |
kWh |
Total read energy load. Summary of all underlying network parts. Presented for substations and bays |
Tot energy losses |
W tot.loss. |
kWh |
|
Tot no load energy losses |
W tot noload loss |
kWh |
Total no-load energy from all underlying transformers. Summary from all underlying network parts. Presented for substations and bays |
Tot reactive energy load |
W react.tot.inp. |
kVAr |
Total reactive power load from energy loads re-calculated with Velander formula. Summary from all underlying parts. Presented for substations and bays |
Tot reactive load losses |
Q tot.loss. |
kVAr |
Total reactive power losses from both load flow losses and no-load losses in cables and transformers. Summary from all underlying parts. Presented for substations and bays |
Tot reactive power |
Q tot |
kVAr |
Total reactive power (power flow). Presented for substations and bays |
Tot reactive power input |
Q tot.inp. |
kVAr |
Total read reactive power load. Summary from all underlying network parts. Presented for substations and bays |