<< Click to Display Table of Contents >> HV Earth fault report |
Substation term:
•Substation ID.
Transformer terms from left to right:
Row 1
•Node point ID.
•Single phase to earth fault current, (A).
•Resistance at high-Ohm earthfault. Standard value can be set with a configuration file (currently 3000 Ohm).
•Single phase to earth fault current, (A), at high Ohm earth-fault.
Row 2
•Capacitive earth fault current, (A).
•Capacitive earth fault current, (A) at high-Ohm earth fault.
Row 3
•Neutral point voltage kV at high-Ohm earth-fault.
•Phase voltage kV for healthy phases at high-Ohm earth-fault.
•Phase voltage kV for faulty phases at high-Ohm earth-fault.
Row 4
•Neutral point voltage kV at rigid fault.
•Phase voltage kV for healthy phases at rigid fault.
Bays / Feeders, Technical Terms from left to right
•Bay ID
•Capacitive earth fault current A
•Single phase earth fault current A
•Capacitive earth fault current A at high Ohm earth fault
•Single phase earth-fault current A at high-Ohm earth fault
•Sum of conductor earth capacitances from upper side A
•Sum of conductor earth capacitances from lower side A
•Sum of other capacitive current in neutral points from upper side A
•Sum of other capacitive current in neutral points from lower side A
•Sum of current from neutral point reactors from upper side A
•Sum of current from neutral point reactors from lower side A
•Sum of reactive current from upper side A
•Sum of reactive current from lower side A
All represented result terms are for a node-point ID. From left to right, these terms are as follows:
•Bay ID
•Node point ID from
•Node point ID to
•Sum of conductor capacitances from upper side, A
•Sum of conductor capacitances from lower side, A
•Sum of other capacitive current in neutral points from upper side, A
•Sum of other capacitive current in neutral points from lower side, A
•Sum of current from neutral point reactors from upper side, A
•Sum of current from neutral point reactors from lower side, A
•Sum of reactive current from upper side, A
•Sum of reactive current from lower side, A
•Sum of resistive current above upper lying reactors, A
•Sum of resistive current under lying reactors, A
Illustration of contribution to earth fault current, e.g. earth fault in Node6 (considering also local neutral point compensation out in the network)
The conductors zero sequence capacitances (re-calculated to capacitive current for printouts):
C_SUM1 = Contribution from the above lying part of the network
C_SUM2 = Ditto for the underlying (summarized to the from-node points)
Other measured capacitive current:
AICSUM1 = Contribution from above lying part of the network
AICSUM2 = Ditto from the underlying network
The neutral points reactor susceptance's (re-calculated to inductive current for printouts):
AILSUM1 = Contribution from above lying part of the network
AILSUM2 = Ditto from the underlying network
Sum of reactive current (capacitive current less the inductive current):
AISUM1 = Contribution from above lying part of the network
AISUM2 = Ditto from the underlying network